In a tall building fire, the escape stair is the only way down. If smoke gets into it, people on every floor above the fire are trapped. A stair pressurization fan pushes clean outside air into the stair, so the air pressure inside is a little higher than on the floors. Smoke cannot push against that, so the stair stays clear.
We supply pressurization fans for towers, hotels, hospitals and malls across the Kingdom, matched to your consultant's fan schedule. Send it to us on WhatsApp, and we will reply with a clear price and datasheets. How many floors does your building have?

The fan sits on the roof or at ground level and takes fresh air from outside, far from any smoke. It blows the air into the stair through a duct, with grilles on several floors. When the fire alarm starts, the fan runs and the stair fills with clean air at a slightly higher pressure.
When someone opens a stair door, the air rushes out through the door instead of smoke rushing in. A relief damper at the top of the stair lets out extra air, so the pressure does not get too high. Many systems use a fan with a speed controller (VFD) and pressure sensors, so the fan speeds up when doors open and slows down when they close.
The same idea, also called stair pressurisation, protects lift shafts and the small lobbies in front of stairs.
The pressure in the stair must be high enough to stop smoke, but low enough that a child or an older person can still open the door.
| Rule | Minimum pressure | Maximum door force |
|---|---|---|
| NFPA 92 and IBC, building with sprinklers | 12.5 Pa (0.05 in. water) | 133 N (30 lbf) |
| NFPA 92 and IBC, building without sprinklers | 25 Pa (0.1 in. water) | 133 N (30 lbf) |
| EN 12101-6, doors closed | 50 Pa | 100 N |
In Saudi Arabia, the design follows the Saudi Fire Code (SBC 801) and the consultant's approved design, and Civil Defense checks it at handover. Your consultant picks the method and the numbers. Our job is to supply a fan that gives the airflow and pressure in the schedule.
The fan must blow in enough air to make up for the air that leaks out through gaps around doors, walls and shafts. Engineers use this formula:
Airflow (m³/s) = 0.827 × leakage area (m²) × √pressure (Pa)
For example, a stair with 0.5 m² of total gaps, kept at 50 Pa, needs about 0.827 × 0.5 × 7.07 = 2.9 m³/s, which is about 10,500 m³/h. Open doors need much more air, so the design also checks the airflow through the open doors. This is why every stair is calculated on its own.
Cased axial fans are compact and move a lot of air. They suit roof units with a short duct into the stair.Industrial axial fans
Centrifugal fans give more pressure for long duct runs or shafts with many grilles.Centrifugal blowers
Some buildings use one fan with a duct shaft down the stair. Very tall buildings may use several fans at different heights, so the pressure stays even from bottom to top.
Many schedules ask for two fans, one running and one standby, so the stair stays safe even if one fan fails.
Airflow in m³/h or m³/s, and the fan pressure in Pa
Fan type: axial or centrifugal, inline or roof
Duty only, or duty and standby
Speed control: fixed speed or VFD
Power supply, normally 380 V three phase, 60 Hz
Extras: weather hood, bird guard, silencer, flexible connectors or relief dampers
The price depends on the airflow, the pressure, the fan type and whether you need standby fans and speed control. Send us your schedule on WhatsApp, and we will price every line in one quote.
Send us your fan schedule or the stair details on WhatsApp. We will match the fans and reply with a clear price and datasheets. Visit our office at 8035 Al Adl Al Waez, Al Amal, Riyadh 12643, open 8:00 to 17:00, call +966 56 259 8137, or email sales@cloudventsa.com. We deliver across the Kingdom, including Riyadh, Jeddah, Dammam, Al Khobar, Makkah and Madinah.
Usually high rise buildings, hospitals, hotels and buildings where the stairs have no windows to the outside. The Saudi Fire Code and your consultant decide which stairs need it.
No. It normally starts with the fire alarm. The building team tests it on a set schedule to make sure the fan starts and the dampers move.
Away from any place smoke can come out, such as exhaust fans, car park ramps or smoke vents. Otherwise, the fan could blow smoke into the stair.
These fans blow clean outside air, so the schedule may not ask for a smoke temperature class. They must still keep running during the fire on a safe power supply. Follow your schedule and the consultant's design.
No. We supply the fans only. Your fire or MEP contractor installs, balances and tests the system, and we share the datasheets and drawings they need.