The CFM Formula
To size an exhaust fan, multiply the volume of the room by the number of times you want to change the air in one hour. The answer is the airflow your fan must move.
In metres: room volume (m³) × air changes per hour = airflow in m³/h. Divide by 1.7 to get CFM.
In feet: room volume (ft³) × air changes per hour ÷ 60 = CFM.
You can also work it the other way, to check a fan you already have. Air changes per hour = fan airflow in m³/h ÷ room volume in m³. For example, a fan of 2,100 m³/h in a room of 150 m³ gives 14 changes per hour.
CFM means cubic feet per minute. Most fan catalogues in Saudi Arabia show m³/h, and many American and Japanese brands show CFM, so the calculator gives you both.
Air Changes per Hour for Common Rooms
An air change means all the air in the room is replaced once. Rooms with steam, smoke, fumes or heat need more changes. These are the guide values the calculator uses. You can change the number if your consultant or the code asks for a different one.
| Room | Air changes per hour |
|---|---|
| Toilet or bathroom | 6 to 10 |
| Shower room | 15 to 20 |
| Laundry room | 15 to 20 |
| Home kitchen | 15 to 20 |
| Commercial kitchen | 20 to 60 |
| Restaurant dining area | 8 to 12 |
| Shop or showroom | 8 to 15 |
| Office | 2 to 6 |
| Classroom | 5 to 7 |
| Hall, majlis or mosque hall | 4 to 8 |
| Workshop | 8 to 10 |
| Welding shop | 15 to 30 |
| Paint booth | 25 to 50 |
| Warehouse | 3 to 6, or 10 and more under a hot metal roof |
| Underground car park | 6 in normal use, 10 in fire mode |
For buildings with people in them all day, the Saudi Mechanical Code (SBC 501) and ASHRAE 62.1 set the fresh air by the number of people and the floor area. Use our result to plan, and follow your project's design where it gives a number.
Exhaust Fan Size Chart
Once you know the airflow, pick the size. For wall fans, the size is the blade size, and the hole in the wall must be a little bigger. This chart uses our TAT steel square wall fans at 60 Hz.
| Blade size | Wall opening | Airflow | About |
|---|---|---|---|
| 20 cm (8 in) | about 24 cm | 1,020 m³/h | 600 CFM |
| 25 cm (10 in) | about 30 cm | 1,500 m³/h | 880 CFM |
| 30 cm (12 in) | about 34 cm | 2,100 m³/h | 1,240 CFM |
| 35 cm (14 in) | about 39 cm | 3,600 m³/h | 2,120 CFM |
| 40 cm (16 in) | about 45 cm | 4,500 m³/h | 2,650 CFM |
| 45 cm (18 in) | about 50 cm | 7,500 m³/h | 4,410 CFM |
| 50 cm (20 in) | ask us | 8,100 m³/h | 4,770 CFM |
For KDK wall fans, the number in the model code is the size in cm, so a 25AUA fits a 300 mm opening. Ceiling fans are sized by the duct and the grille. The TAT 50 to 120 QCA models take a 105 mm duct and a 300 mm grille, and the 160 to 300 models take a 155 mm duct and a 385 mm grille. The KDK 24CUH and 24CHH take a 98 mm duct and a 300 mm grille. Wall mounted exhaust fans
Three Examples from Real Jobs
A Villa Bathroom in Riyadh
The bathroom is 2.5 m long, 2 m wide and 3 m high, so it holds 15 m³ of air. At 10 changes per hour, that is 150 m³/h, or about 88 CFM. ASHRAE 62.2 asks for at least 50 CFM in a home bathroom, so 88 CFM passes. A ceiling fan of 80 to 120 CFM is a good fit, such as the TAT 120 QCA or the KDK 24CHH. Bathroom exhaust fans
A Restaurant Hood in Jeddah
The hood is 3 m long, against a wall, over a charcoal grill. Charcoal counts as extra heavy cooking, at 550 CFM for every foot of hood. 3 m is about 9.8 ft, so the hood needs about 5,400 CFM, or 9,200 m³/h. This needs a grease rated fan, such as an upblast roof fan or a kitchen blower, plus make up air to replace what the hood takes out. Kitchen exhaust fans
A Warehouse in the Second Industrial City
The warehouse is 40 m long, 25 m wide and 8 m high, so it holds 8,000 m³ of air. Under a metal roof in a Riyadh summer, plan 10 changes per hour. That is 80,000 m³/h, or about 47,000 CFM. With TAT 50 cm steel wall fans at 8,100 m³/h each, you need 10 fans. Roof fans or large axial fans can do the same job with fewer units. Industrial axial fans
Rules for Bathrooms and Kitchens
Some rooms have their own minimum, and the calculator checks it for you.
Home bathroom: at least 50 CFM when the fan runs on demand, or 20 CFM if it runs all day (ASHRAE 62.2). A quick check from HVI for bathrooms up to about 9 m² is 1 CFM for each square foot of floor, which is about 11 CFM for each square metre.
Public toilets in offices, malls and mosques: 70 CFM for each toilet or urinal when the fan runs on demand, or 50 CFM if it runs all day (ASHRAE 62.1).
Home cooker hood: about 100 CFM for each foot of cooker width against a wall, and 150 CFM for an island. A 60 cm cooker is about 2 ft, so it needs about 200 CFM. A 90 cm cooker needs about 300 CFM. Kitchen hoods
Restaurant hood: 200 to 550 CFM for each foot of hood, from light cooking like ovens up to charcoal and wood. In Saudi Arabia, the MOMAH Chimney Guide and NFPA 96 also set rules for grease fans, filters and where the exhaust may discharge.
When the Number Is Not Enough
The airflow is the first step, not the last. Four more things decide which fan really works.
Pressure. Every metre of duct, every bend, filter and louver slows the air. A wall fan that moves 2,100 m³/h in free air moves much less at the end of a long duct. For long runs, use an inline fan or a centrifugal blower.
Power. Saudi Arabia runs on 60 Hz. Choose single phase for homes and small shops, and three phase for large fans.
Noise. A bigger fan running slow is quieter than a small fan running flat out. For bedrooms, hotels and offices, ask for the sound level.
Heat and grease. Kitchen exhaust needs grease rated fans, and smoke exhaust needs fans tested for fire.
Send us your result, the duct length and a photo of the place, and our team will check all four before we quote.
Frequently Asked Questions
What size exhaust fan do I need?
Work out the airflow first with the calculator, then pick the size from the chart above. As a guide, a home kitchen wall usually takes a 25 or 30 cm fan, and a bathroom takes an 80 to 120 CFM ceiling fan. If you are replacing an old fan, measure the hole in the wall and use the same size.
What is CFM?
CFM stands for cubic feet per minute. It tells you how much air a fan moves. A bigger number means a stronger fan. In m³/h, the same figure is about 1.7 times larger.
How do I convert CFM to m³/h?
Multiply CFM by 1.7. For example, 100 CFM is about 170 m³/h. To go the other way, multiply m³/h by 0.59. You can also use our converter. CFM to m³/h converter
Is a bigger fan always better?
No. A fan that is too strong for a small room is noisy, uses more power and can pull dust and hot air in through doors and gaps. Pick the airflow you need, then add a little margin for the duct.
How many air changes does a warehouse need in summer?
For general air, 3 to 6 changes per hour is common. Under a metal roof in Riyadh or Dammam, where the air inside gets very hot, many buyers plan 10 or more to pull the heat out. Big HVLS fans can also make the space feel cooler without more exhaust.
Can you check my numbers?
Yes. Send us the room size, what the room is used for and the duct length on WhatsApp. We will check the airflow and the pressure, and send you a model with a clear price.
Get the Right Fan for Your Result
Send us your result, BOQ or fan schedule, and we will reply with a model, datasheet and price. Visit our office at 8035 Al Adl Al Waez, Al Amal, Riyadh 12643, open 8:00 to 17:00, or message us on WhatsApp, call +966 56 259 8137, or email sales@cloudventsa.com. We deliver across the Kingdom, including Riyadh, Jeddah, Dammam, Al Khobar, Makkah and Madinah.